Typical Applications

 

Corridor Spacing

Open Office Spacing

Fluorescent battery pack: PS600QD
Fluorescent fixture: Lensed Troffer
Lamp type: F32T8
 

Fluorescent battery pack: PS1400QD
Fluorescent fixture: 2 x 4 Parabolic
Lamp type: F32T8


Meets Life Safety Code standard minimum illuminance of 0.1 FC and average illuminance of 1.0 FC. Assumes 3T8 lamps in each fixture, 8W x 100L corridor, ceiling height of 9, and reflectances of 80/50/20.

One Footcandle Average Spacing Guidelines -
2 X 4 Fixture in a Corridor

  T8 Lensed Troffer T8 Direct/Indirect T8 Parabolic
PS300QD 24 18 21
PSQ500QD 35 28 32
PS600QD 43 34 40
PS1400QD 57 59 53

Meets Life Safety Code standard minimum illuminance of 0.1 FC and average illuminance of 1.0 FC. Assumes 3T8 lamps in each fixture, 100W x 100L open office, ceiling height of 9, and reflectances of 80/50/20.

One Footcandle Average Spacing Guidelines -
2 X 4 Fixture in an Open Office

  T8 Lensed Troffer T8 Direct/Indirect T8 Parabolic
PS300QD 16 13 17
PSQ500QD 29 21 27
PS600QD 35 26 34
PS1400QD 47 47 45

Click here for additional recommended Corridor, Open Office/Industrial Spacing Guidelines (1 FC average and 1 FC minimum illuminance)